TG - E5_C Series - Transfer Output and Simple Transfer Output Function

Modified on Tue, 4 Feb at 3:58 PM

Purpose

This document outlines the procedure for utilizing the Transfer Output and Simple Transfer Output functions on the temperature controller.


Explanation 

The Transfer Output Function enables the transfer of a current or voltage signal that represents the process value, set point, or other relevant data. If the control output is configured as a linear current output, it can also serve as a Simple Transfer Output, allowing the transfer of data using a current signal.


Supported devices for the Transfer Output Function

• E5CC Series with option number 006
• E5CC-B Series with option number 006
• E5EC/E5AC Series with option numbers 011, 012, 013, or 014
• E5EC-B Series with option numbers 011 or 014


Supported devices for the Simple Transfer Output Function

• E5CC-U Series with Linear Current Output (CX)
• E5DC Series with linear Current Output (CX)
• E5DC-B Series with Linear Current Output (CX)
• E5GC Series with Linear Current Output (CX)


Transfer Output Procedure

There are six types of data that can be output, in either as a Current Output (4-20mA) or a Voltage Output (1-5V). See explanation below. 


Transfer Output TypeDisplaySetting Range
OFF (default)OFF---
Set pointSPSP lower limit to SP upper limit
Set point during SP ramp
SP-MSP lower limit to SP upper limit
PVPVInput setting range lower limit to input setting range upper limit or Scaling lower limit to scaling upper limit 
MV monitor (heating)MV-5.0 to 105.0 (heating/cooling control: 0.0 to 105.0)
MV monitor (cooling)
C-MV0.0 to 105.0
Valve openingV-M-10.0 to 110.0

1. Press the Level key for a least 3 seconds on the Operation Level to go to the Initial Setting Level.

*All settings are done in the Initial Setting Level.


2. Press the Mode key several times until reaching the Transfer Output Signal Type display (TRST). 


3. Press the Up and Down keys to select either 1-5V or 4-20. 


4. Press the Mode Key key several times until reaching the Transfer Output Type display (TR-T) and select the required output type from options shown on the table above.  

*Example: Output the Process Value, Then set as PV.


5. Press the Mode key several times until reaching the Transfer Output Upper Limit display (TR-H).


6. Press the Up and Down keys to set the Scaling Value for the Upper limit. 

*Example: Output the Process Value from -50°C to 200°C, Then set the 200 value. 


7. Press the Mode key several times until reaching the Transfer Output Lower Limit display (TR-L)


8. Press the Up and Down keys to set the Scaling Value for the Lower limit. 

*Example: Output the Process Value from -50°C to 200°C, Then set the -50 value. 


Simple Transfer Output Procedure

There are five types of data that can be output as a Current Output (4-20mA). See explanation below. 


Transfer Output TypeDisplaySetting Range
Simple transfer SPT-SP
SP lower limit to SP upper limit
Simple transfer ramp SP
TSPM
SP lower limit to SP upper limit
Simple transfer PV
T-PV
Input setting range lower limit to input setting range upper limit or Scaling lower limit to scaling upper limit 
Simple transfer MV monitor (heating)T-MV-5.0 to 105.0 (heating/cooling control: 0.0 to 105.0)
Simple transfer MV monitor (cooling)
TCMV0.0 to 105.0



Move to the Advanced Setting Level to enable the Simple Transfer Output. 

1. Press the Level key for a least 3 seconds on the Operation Level.


2. Press the Level key for several times until reaching the Move to Advanced Function Setting Level parameter (AMOV). 


3. Press the Up and Down keys to enter password -169. 

 

4. On the Advanced Function Setting Level, press the Mode several times until reaching the Control Output 1 Assignment display (OUT1). 


5. Press the Up and Down keys to select the required output type from options shown on the table above. 

*Example: Output the SP, Then set as T-SP


6. Go back to the Initial Setting Level by pressing the Level key for a least 1 second. 


7. Pres the Mode key for several times until reaching the Simple Transfer Output 1 Upper Limit parameter (O1TH). 


8. Press the Up and Down keys to set the Scaling Value for the Simple Transfer Upper limit. 

*Example: Output the SP range from -50°C to 200°C, Then set the 200 value


9. Pres the Mode key for several times until reaching the Simple Transfer Output 1 Lower Limit parameter (O1TL). 


10. Press the Up and Down keys to set the Scaling Value for the Simple Transfer Lower limit. 

*Example: Output the SP range from -50°C to 200°C, Then set the -50 value


Date/Revision History

First review 9/05/2024 V1.0

2nd review 12/19/2024 V1.1

3rd review 01/13/2


Author:

Andrea Balderrama, Technical Support Engineer


References

Digital Temperature Controllers User's Manual

Digital Temperature Controller Datasheet

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article