Purpose
This document provides instructions for resetting the parameters of the E5_C Series temperature controllers to their default settings.
Explanation
The E5_C Series controllers offer a feature to erase all current programming and revert to default parameters when necessary.
Supported devices
Requirements
Procedure
Set the Initial Setting/Communications Protect parameter to 0 to enable moving to Advanced Function Setting Level.
1. Go from the Operation Level to the Protect Level. Press the Level Key and Mode Key simultaneously for at least 3 seconds.
The display will change to:
2. Scroll to the Initial Setting/Communications Protect parameter showed below and change it to 0.
3. Go back to the Operation Level. Press the Level Key and Mode Key simultaneously for at least 1 second.
Move to the Advanced Function Setting Level
4. Press the Level Key for a least 3 seconds on the Operation Level.
The display will show the first parameter on the Initial Setting Level:
5. Press the Mode Key for several times until reaching the Move to Advanced Function Setting Level parameter shown below:
6. Press the Up and Down keys to enter password -169.
The display will show the first parameter on the Advanced Function Setting Level.
7. Change the Parameter Initialization parameter to "FACT" using the Up and Down keys.
8. Done! The Controller is now in Factory Settings.
Date/Revision History
First review 9/05/2024 V1.0
2nd review 12/19/2024 V1.1